Formula Petungan HVAC

微信截图_20220628084907

I, suhu:

Celsius (C) lan Fahrenheit (F)

Fahrenheit = 32 + Celcius × 1,8

Celsius = (Fahrenheit -32) /1.8

Kelvin (K) lan Celsius (C)

Kelvin (K) = Celsius (C) +273,15

II, konversi tekanan:

Mpa, Kpa, pa, bar

1Mpa = 1000Kpa;

1 Kpa = 1000 pa;

1 Mpa = 10 bar;

1 bar = 0,1 Mpa = 100 Kpa;

1atmosfer=101.325Kpa=1bar=1Kilogram;

1 bar = 14,5 psi

1psi = 6,895 Kpa

1 kg/cm2=105=10 mH2O=1 bar=0,1 MPa

1 Pa = 0,1 mmH2O = 0,0001 mH2O

1 mH2O = 104 Pa = 10 kPa

III, kacepetan angin, konversi volume

1CFM =1,699 M³/H=0,4719 l/s

1M³/H=0,5886CFM

1l/s=2.119CFM

1FPM=0,3048 m/min=0,00508 m/s

IV, Kapasitas lan daya pendinginan:

1KW = 1000 W

1KW=861Kkal/h=0,39 P(kapasitas pendinginan)

1 W = 1 J/s

1USTR=3024Kkal/jam=3517W(kapasitas pendinginan)

1 BTU = 0,252 kkal/jam = 1055J

1 BTU/H=0,252 kkal/jam

1 BTU/H=0.2931W(kapasitas pendinginan)

1MTU/H = 0.2931KW (kapasitas pendinginan)

1HP (listrik) = 0,75KW (listrik)

1KW (listrik) = 1.34HP (listrik)

1 RT (kapasitas pendinginan) = 3.517KW (kapasitas pendinginan)

1KW (kapasitas pendinginan= 3,412 MBH

1 P (kapasitas pendinginan= 2200 kkal/jam = 2,56KW

1 kkal/jam = 1,163 W

V,ACkekandelan instalasi lan kapasitas cooling:

1.5mm2=12A-20A(2650~4500W) 1P~2P

2.5mm2=20-25A(4500~5500W) 2P

4mm2=25-32A(5500~7500W) 2P~3P

6mm2=32-40A(7500~8500W) 3P~4P

VI, formula penghitungan refrigeran:

1. Pilihan katup ekspansi: ton dingin + tunjangan 1,25%.

2. Daya tekan: 1P = 0.735kW

3. Pengisian refrigeran: Kapasitas pendinginan (KW) ÷ 3,516 x 0,58

4. Aliran banyu saka hawa adhem: Kapasitas pendinginan (KW) ÷ prabédan suhu ÷ 1,163

5. Laju aliran banyu pendinginan mesin sekrup sing adhem banyu: Kapasitas pendinginan (KW) × 0.86÷ prabédan suhu

6. Tingkat aliran banyu pendinginan mesin sekrup sing adhem banyu:(kapasitas pendinginanKW+ daya tekan) ×0.86÷ prabédan suhu

7. Nilai kalor kotor QT=QS+QL

8. Pendinginan udara: QT = 0.24*∝*L*(h1-h2)

9. Pendinginan udara panas sing signifikan: QS = Cp * ∝ * L * (T1-T2)

10. Panas laten saka pendinginan udara: QL=600*∝*L*(W1-W2)

11,Banyu bekuvolume:L/sV1= Q1/(4,187△T1)

12. Volume banyu pendingin: L/sV2=Q2/(4.187△T2)=(3.516+KW/TR)TR,Q2=Q1+N=TR*3.516+KW/TR*TR=(3.516+KW/TR) *TR

13. Efisiensi pendinginan: EER = Kapasitas pendinginan (Mbtu/h)/konsumsi daya (KW);COP = Kapasitas pendinginan (KW) / konsumsi daya (KW)

14. Kinerja beban pendinginan parsial: NPLV=1/(0.01/A+0.42/B+0.45/C+0.12/D)

15. Arus beban penuh (tiga fase): FLA=N/√3 UCOSφ

16. Volume udara segar: Lo = nV

17. Udarapasokan volume: L=Qs/〔Cp*∝*(T1-T2)〕

18. Daya kipas: N1=L1*H1/(102*n1*n2)

19, Daya pompa banyu: N2 = L2 * H2 * r / (102 * n3 * n4)

20. Diameter pipa: D=√4*1000L2/(π*v)

21, Area saluran: F=a*b*L1/(1000u)