I, suhu:
Celsius (C) lan Fahrenheit (F)
Fahrenheit = 32 + Celcius × 1,8
Celsius = (Fahrenheit -32) /1.8
Kelvin (K) lan Celsius (C)
Kelvin (K) = Celsius (C) +273,15
II, konversi tekanan:
Mpa, Kpa, pa, bar
1Mpa = 1000Kpa;
1 Kpa = 1000 pa;
1 Mpa = 10 bar;
1 bar = 0,1 Mpa = 100 Kpa;
1atmosfer=101.325Kpa=1bar=1Kilogram;
1 bar = 14,5 psi
1psi = 6,895 Kpa
1 kg/cm2=105=10 mH2O=1 bar=0,1 MPa
1 Pa = 0,1 mmH2O = 0,0001 mH2O
1 mH2O = 104 Pa = 10 kPa
III, kacepetan angin, konversi volume
1CFM =1,699 M³/H=0,4719 l/s
1M³/H=0,5886CFM
1l/s=2.119CFM
1FPM=0,3048 m/min=0,00508 m/s
IV, Kapasitas lan daya pendinginan:
1KW = 1000 W
1KW=861Kkal/h=0,39 P(kapasitas pendinginan)
1 W = 1 J/s
1USTR=3024Kkal/jam=3517W(kapasitas pendinginan)
1 BTU = 0,252 kkal/jam = 1055J
1 BTU/H=0,252 kkal/jam
1 BTU/H=0.2931W(kapasitas pendinginan)
1MTU/H = 0.2931KW (kapasitas pendinginan)
1HP (listrik) = 0,75KW (listrik)
1KW (listrik) = 1.34HP (listrik)
1 RT (kapasitas pendinginan) = 3.517KW (kapasitas pendinginan)
1KW (kapasitas pendinginan)= 3,412 MBH
1 P (kapasitas pendinginan)= 2200 kkal/jam = 2,56KW
1 kkal/jam = 1,163 W
V,ACkekandelan instalasi lan kapasitas cooling:
1.5mm2=12A-20A(2650~4500W) 1P~2P
2.5mm2=20-25A(4500~5500W) 2P
4mm2=25-32A(5500~7500W) 2P~3P
6mm2=32-40A(7500~8500W) 3P~4P
VI, formula penghitungan refrigeran:
1. Pilihan katup ekspansi: ton dingin + tunjangan 1,25%.
2. Daya tekan: 1P = 0.735kW
3. Pengisian refrigeran: Kapasitas pendinginan (KW) ÷ 3,516 x 0,58
4. Aliran banyu saka hawa adhem: Kapasitas pendinginan (KW) ÷ prabédan suhu ÷ 1,163
5. Laju aliran banyu pendinginan mesin sekrup sing adhem banyu: Kapasitas pendinginan (KW) × 0.86÷ prabédan suhu
6. Tingkat aliran banyu pendinginan mesin sekrup sing adhem banyukapasitas pendinginanKW+ daya tekan) ×0.86÷ prabédan suhu
7. Nilai kalor kotor QT=QS+QL
8. Pendinginan udara: QT = 0.24*∝*L*(h1-h2)
9. Pendinginan udara panas sing signifikan: QS = Cp * ∝ * L * (T1-T2)
10. Panas laten saka pendinginan udara: QL=600*∝*L*(W1-W2)
11,Banyu bekuvolume:L/sV1= Q1/(4,187△T1)
12. Volume banyu pendingin: L/sV2=Q2/(4.187△T2)=(3.516+KW/TR)TR,Q2=Q1+N=TR*3.516+KW/TR*TR=(3.516+KW/TR) *TR
13. Efisiensi pendinginan: EER = Kapasitas pendinginan (Mbtu/h)/konsumsi daya (KW);COP = Kapasitas pendinginan (KW) / konsumsi daya (KW)
14. Kinerja beban pendinginan parsial: NPLV=1/(0.01/A+0.42/B+0.45/C+0.12/D)
15. Arus beban penuh (tiga fase): FLA=N/√3 UCOSφ
16. Volume udara segar: Lo = nV
17. Udarapasokan volume: L=Qs/〔Cp*∝*(T1-T2)〕
18. Daya kipas: N1=L1*H1/(102*n1*n2)
19, Daya pompa banyu: N2 = L2 * H2 * r / (102 * n3 * n4)
20. Diameter pipa: D=√4*1000L2/(π*v)
21, Area saluran: F=a*b*L1/(1000u)